Use the dropdown filters on the right, to swiftly find your product... Left to right.
Product Code: LMO24-111C2
In Stock
Microcontroller-based oil burner controls for the startup, supervision and control of forced draft oil burners in intermittent operation. Maximum oil throughput up to 30 kg/h, also above 30 kg/h on some versions.
The LMO14, LMO24, LMO44 and this Data Sheet are intended for use by OEMs which integrate the burner controls in their products.
The LMO are designed for the startup and supervision of 1- or 2-stage forced draft oil burners in intermittent operation. Yellow-burning flames are supervised with photo resistive detectors QRB1 / QRB3 or yellow flame detector QRB4, blue-burning flames with blue flame detector QRC.
In terms of housing dimensions, electrical connections and flame detectors, the LMO are identical with the LOA oil burner controls.
Features
Supply Voltage | AC 230 V |
---|---|
Frequency (Hz) | 50/60 |
Fuel Valve Stages | 2 |
Burner Capacity | <30 Kg/h |
Remote Reset | Yes |
Bridging Contact | Yes |
Waiting Time (TW Max | 2.5s |
Pre-purge Time | 15s |
Purge Time | 16s |
Ignition Safety Time (TSA Max) | 10s |
Pre-Ignition Time (t3 Min) | 15s |
Post-Ignition Time (t3n Max) | 10s |
Interval From Flame Signal To Release Of Fuel Valve | 15s |
Weight (kg) | 0.2 |
Warranty | 12 Months |
UK Mainland | Order by 2pm for Next Day Delivery* |
---|---|
Under £25.00 | £4.50 |
Over £25.00 | FREE |
UK Highlands & Islands | Order by 2pm for Next Day Delivery* |
---|---|
Under £80.00 | £15.00 |
Over £80.00 | FREE |